Dynamic pass box manual

h5

1. Specifications:

    Model: S1

    Voltage: AC220V 50HZ

    With lock voltage: DC12V

    Door magnetic type: dry contact signal, the door is closed.

   1. Wiring diagram:

   As shown in the figure, correctly connect the power supply, output board, display board, main and auxiliary door locks and main and auxiliary door magnetics, fans, lighting lamps, and germicidal lamps.

h1
h2

Main controller DIP switch settings:

1.1# is dialed to "ON" for normally open, and dialed to "OFF" for normally closed.

2.2#, 3# dial code reserved, dial to OFF;

3.4# is dialed to "ON", the timing unit is "seconds"; dialed to "OFF", the timing unit is "minutes".

LCD panel DIP switch settings:

The DIP switch No. 1 on the main door display board is set to "ON", and the DIP switch No. 2 on the auxiliary door display board is set to "ON". Do not set it wrong.

Note: The main door is defined as the goods entry door (communication address is 1), and the secondary door is defined as the exit door (communication address is 2).

3. Button description:

1. Power button: After connecting the power, press and hold this button for 2 seconds to turn on, the LCD display of the main door and the auxiliary door will be lit, as shown in the display panel interface above, press and hold for 2 seconds to shut down in the power-on state.

2. Blowing shower key: 1) If the blowing shower time P2 is set to 00, the blowing shower is in manual mode, which is manually opened and manually closed, but cannot be opened when the door is opened.

2) If the blowing shower time P2 is set to be greater than 00, the blowing shower is in automatic mode, which is automatically turned on and automatically turned off. In this mode, the shower key is shielded and the operation is invalid. For example, if P2 is set to 10, and parameter P4 is set to 1, the air shower will run when the main door and the auxiliary door are closed. After the 10-minute countdown is over, the air shower will automatically stop. If the parameter P4 is set to 0, only the main door will be closed. The air shower only operates, and the air shower does not operate when the auxiliary door is closed. When the air shower is running, the doors are locked, the fan on the LCD screen rotates, and the lock icon is in a locked state and flashes.

3. Sterilization key: 1) If the sterilization time P3 is set to 00, the sterilization is in manual mode, which is manually opened and manually closed, but cannot be opened when the door is opened.

          2) If the sterilization time P3 is set to be greater than 00, the sterilization is in automatic mode, which is manually turned on and automatically turned off. For example, when P3 is set to 10, after closing the door, press the "sterilization button", the germicidal lamp starts to work, the door is locked, and the germicidal lamp on the LCD screen flashes, and the lock icon is locked and flashes. After the 10-minute countdown is over, the sterilization will automatically stop running.

          3) If the sterilization mode parameter P5 is set to 01, the sterilization lamp will automatically start when the door is closed, and will automatically turn off when the sterilization time is over.

          4) In the non-setting state, press and hold the "sterilization button" for 2 seconds to enter the viewing sterilization time mode, and the digital area displays the total time of the germicidal lamp, such as "01 20", which means that the germicidal lamp has been used for 1 day and 20 Hour. After replacing the germicidal lamp, you can long press the "sterilization button" for 6 seconds in the non-setting state to reset the time.

4. Door open key: At any time, the door can be opened only when the lock icon displayed on the LCD does not flash and is in the lock open state.

1) In normally closed mode, in the case of no air shower and sterilization operation, in the non-set state, press the door open button, the door lock will be opened, the lock icon on the LCD display will be in the open state, and within the door delay time, the door will be opened. It can be opened. Once the door is opened, the door lock to the door is locked, and the door cannot be opened to achieve an interlocking effect. When the door delay time countdown expires, the magnetic lock is powered on, waiting for the door to close and lock the door.

2) In the normally open mode, when the air shower and sterilization are not running, all the magnetic locks cannot be powered, and the doors can be opened. Once one of the doors is opened, the magnetic lock on the opposite door will be locked immediately, and the lock icon on the liquid crystal display will appear as locked state. In the process of air shower or sterilization, when it is necessary to open the door urgently, press and hold the door button for 2 seconds, the air shower and sterilization will stop running, the magnetic lock will not be powered, and the door can be opened.

Note: When the door is opened, if it is not closed within 15 seconds, the buzzer will beep every 2.5 seconds to remind the door to close.

5. Call key: press this key, the buzzer on the opposite door panel will send out a "di" calling sound to remind the other party to pay attention. Press the "call key" again to cancel the call reminder, press the "call key" of the opposite door to cancel the call reminder, and open or close the opposite door in time to cancel the call reminder.

6. Setting button: After power on, press and hold the "setting button" for 2 seconds to enter the setting mode. Please refer to "Parameter Setting/Viewing Steps".

7. Lighting function: the light is on when any door is opened, and the light is off when both doors are closed.

Fourth, parameter description:

P1: 05/-- In normally closed mode, P1 is the door opening delay time (unit: seconds), the setting range is 5~10 seconds, the default factory setting is 5 seconds, that is, when the fan and sterilization are not running, after pressing the door open button The countdown is 5 seconds. Within 5 seconds, the magnetic lock will not be powered, the door can be opened, and after 5 seconds, the magnetic lock will be powered, wait for the door to close and lock the door.

In the normally open mode, the P1 parameter is meaningless and cannot be set, and always displays --.

P2: 10 Blowing shower time (unit: minutes), the setting range is 00~99 minutes. When set to 00, it is manual mode, blowing

The shower needs to be manually turned on and turned off manually; when the setting is greater than 00, it is in automatic mode, which is automatically turned on and automatically turned off. The default factory setting is 10 minutes, that is, after the blower is automatically turned on, it will be automatically turned off after 10 minutes.

P3: 30 Sterilization time (unit: minutes), the setting range is 00 to 99 minutes. When it is set to 00, it is manual mode, and sterilization needs to be manually turned on and off; when it is set to more than 00, it is automatic mode, and it is turned on manually or automatically (determined by the P5 parameter), and it is automatically turned off. If set to 10, after the sterilization is turned on, it will automatically turn off after 10 minutes.

P4: 01 Sub-door working mode. When set to 00, blow shower (and sterilize) when the main door is closed [whether sterilization is determined by the P5 parameter], and do not blow (and sterilize) when the secondary door is closed [whether sterilization is determined by the P5 parameter]; when set to 01 , the main door and the auxiliary door are both blowing (and sterilizing) when they are closed [whether or not to sterilize is determined by the P5 parameter].

P5: 00 Automatically start the sterilization mode, when it is set to 00, the sterilization will not start after the door is closed. When set to 01, the air shower and sterilization will also start automatically after the door is closed.

P6: 00 Display mode, when set to 00, when both blowing shower and sterilization are in automatic mode, the shorter one of blowing shower time and sterilization time will be displayed. After the shorter countdown is over, the longer one will be displayed. The item counts down until the end; when it is set to 01, the shower time will be displayed when both the shower and sterilization are in automatic mode; when it is set to 02, the sterilization time will be displayed. If one of them is in manual mode, the time of the item in automatic mode will be displayed; if only the air shower is running and the air shower is in manual mode, the cumulative running time of the air shower will be displayed, if only sterilization is running and the sterilization is in manual mode, it will be displayed 00.

P7: 00 Detection mode, set to 00 is non-detection mode, the main and auxiliary doors must be closed for blowing shower or sterilization to run; when set to 01, it enters detection mode, no matter the main and auxiliary doors are open or closed, blowing and sterilization can be run.

5. Parameter setting/viewing steps:

1. After power on, press and hold the "Setting button" for 2 seconds to enter the setting mode.

2. In the setting state, short press the setting key to switch the parameters to be set, P1~P7.

3. In the setting state, short press the shower button to reduce the size of the parameter, and long press to decrease the value.

4. In the setting state, short press the sterilization button to increase the size of the parameter, and long press to increase.

5. After setting, short press the setting button again to save and automatically switch to the next parameter.

6. Press and hold the setting button again for 2 seconds to exit the setting state. If there is no operation within 6 seconds after entering the setting state, it will automatically exit the setting state.

7. Except for the P1 parameter in the normally closed mode, the main and auxiliary doors can be changed, other parameters can only be changed on the main door, and the auxiliary door can only be viewed. 

6. Troubleshooting:

1. After power on, press and hold the "power button" for 2 seconds, if there is no response, please confirm whether there is 220V power supply from the outside and whether the voltage is normal.

2. If the external power supply is normal, a professional is required to check, and it is necessary to check whether the connection line between the internal display panel and the output board is normal.

3. If the internal connection line is normal, the communication circuit on the control board is faulty.

4. During use, it is found that all key operations are invalid, and the triangular alarm icon on the display panel flashes, and the buzzer emits a rapid "di" sound, indicating a communication failure, internal wiring problems, or controller failure. .

5. If the operation is chaotic, please check whether the parameters are set correctly. For the parameter setting method, please refer to the parameter setting/viewing steps. 